产品库

KFD2-UT2-2 P+F信号处理器

产品信息
如有需要,欢迎来电洽谈 上海桂伦 销售工程师 王勇 -8022 Technical Data: KFD2-UT2-2
产品阐述
Current output 0/4 mA ... 20 mA
General specifications
Signal typeAnalog input
Supply
Connectionterminals 14+, 15- or power feed module/Power Rail
Rated voltage20 ... 30 V DC
Ripplewithin the supply tolerance
Power loss/power consumption≤ 1.5 W / 1.5 W
Input
Connectionterminals 1, 2, 3; 4, 5, 6
RTDtype Cu10, Cu50, Cu100, Pt10, Pt50, Pt100, Pt500, Pt1000, Ni100 (EN 60751: 1995)

type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (P50353-92)
Measuring currentapprox. 200 µA with RTD
Types of measuring2-, 3-wire connection
Lead resistancemax. 50 Ω per lead
Measuring circuit monitoringsensor burnout, sensor short-circuit
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)

type L (DIN 43710: 1985)

type TXK, TXKH, TXA (P8.585-2001)
Cold junction compensationexternal and internal
Measuring circuit monitoringsensor burnout
Voltageselectable within the range -100 ... 100 mV
Potentiometer0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
Input resistance≥ 1 MΩ (-100 ... 100 mV)
Output
Connectionoutput I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-)

output II: terminal 10: source (-), sink (+), terminal 11: source (+), terminal 12: sink(-)
Output I, IIAnalog current output
Current range0 ... 20 mA or 4 ... 20 mA
Fault signaldownscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
Sourceload 0 ... 550 Ω

open-circuit voltage ≤ 18 V
SinkVoltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V,

series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage.

The maximum value of the resistance is (V - 5)/0.0215 Ω.
Transfer characteristics
Reaction timesensor burnout and sensor short circuit selected where appropriate

mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Conformity
Electromagnetic compatibilityNE 21:2006
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degreeIP20
Massapprox. 130 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
信息声明:本产品供应信息由仪器网为您整合,供应商为(武汉西尔福贸易有限公司),内容包括 (KFD2-UT2-2 P+F信号处理器)的品牌、型号、技术参数、详细介绍等;如果您想了解更多关于 (KFD2-UT2-2 P+F信号处理器)的信息,请直接联系供应商,给供应商留言!